Wiring Two Way Light Switcht

Electrolesk's Practical Wiring

Wiring of Two Way Light Switches are now common for Electrical Installation Work. Here we are considering wiring a Two Way Light Switch for 50Hz, 230V AC Power Supply. Installation work described here is according to British Standards [ IEE Regulations and Practice ] and also is useful as a DIY Guide

"Electric and magnetic forces. May they live for ever, and never be forgot, if only to remind us that the science of electromagnetics, in spite of the abstract nature of its theory, involving quantities whose nature is entirely unknown at the present, is really and truly founded on the observations of real Newtonian forces, electric and magnetic respectively"

- Oliver Heaviside (1850-1927) — Physical Mathematician
Practical Guide to Electrical Installations

Wiring Two Way Light Switch

ELECTROLESK

Wiring Diagram
Two Way Light Switch Wiring Circuit - Diagram
Wiring Diagrams 2 way Light Switch Wiring - PDF Diagram

Wiring of Two Way Light switches are now common for Electrical Installation Work.

Here we are considering wiring a Two Way Light Switch for 50Hz, 230V AC Power Supply.

Installation work described here is according to British Standards [ IEE Regulations and Practice ] and also is useful as a DIY Guide

All about practical installation methods for Two Way Light Switch
Material Requirement
Two Way Light Switcht Wiring
Material Requirement

For Industrial applications, 1.5 mm2 [called as 1.5 mm squared] Cross sectioned double insulated Cu [Copper] Cables [Cu/PVC/PVC] are used for the Phase [Live ] and the Neutral cables.

For Residential applications, 1.0 mm2 Cross sectioned double insulated Cu [Copper] Cables [Cu/PVC/PVC] are commonly used for the Phase and the Neutral cables.

Earth [Ground ]cable should be 2.5mm2 single insulated Cu[Copper] Cables [Cu/PVC] for both Industrial or Residential type of applications.

Cable lengths for the above circuits will be such that voltage drop along the cables will be with in the approved limits of 10% of Supply Voltage.

Accessory Requirement
Two Way Light Switch Wiring
Accessory Requirement

PVC Boxes to install the 2 Way Light Switches-02 nos

One Gang 2 Way Light Switches-02 nos

PVC Ceiling Rose [3 terminal type] -01 nos

Lamp Holder-01 nos

MCB 6A -01 nos [ from a Distribution Board already installed]

Preparation
Two Way Light Switch Wiring
Preparation

Install the socket outlet boxes at the required positions.

Lay PVC conduits from the Distribution Board to the receptacle positions.

The conduits can be embedded into the wall structure and or lay outside, clipped to the wall or structure.

Instead of PVC conduits and switch boxes, GI conduits and switch boxes are being used for Industrial type of installations where you need protection for cables from physical damage.

In some wooden structured buildings, the cables are installed inside panels without conduits being used.

The Cables should be colour coded correctly for Phase[Live],Neutral and Earth.

Method of Two Way Light Switch Wiring
Two Way Light Point Wiring
Method of Wiring-Residential

Make sure that the Power is isolated [ shut down] to the Distribution board or any circuit you will be working with.

Connect the Phase [L] wire to the outgoing side of a 6A or a 10A [Maximum] MCB from the Distribution Board [DB].

Draw the Phase wire to the nearest Switch box and connect to the common terminal of the first Two way switch.

Connect two separate phase wires to the remaining terminals of the first 2 Way switch and draw them to the other Switch box position and connect to two separate terminals of the second 2 Way switch.

Connect the common terminal of the second 2 Way switch to a Phase wire and draw that wire to the Ceiling rose.

Now connect a Neutral [N] wire to the Neutral Link provided in the DB and draw it to the Ceiling rose.

It is good practice to number the Phase and the Neutral wires at the DB for easy identification as one circuit.

Connect the Earth [E] wire to the Earth link provided in the Distribution Board.

Draw these Neutral and Earth wires directly to the ceiling rose and use the two spare terminals to connect these wires separately.

Now all the 3 terminals of the Ceiling rose are connected.

Take the lamp holder and a short length of 3 core flexible cable and connect the Phase and Neutral wires to the holder.

If the holder is a pin type one , then either the Phase or the Neutral can be connected to any terminal.

If the holder is Screw type, then the Neutral should be connected to the threaded part of the terminal and the Phase to the other terminal.

Normally the Earth wire is used for a Lamp fitting with metal parts to be connected.

Then connect the Phase, Neutral and Earth wires of the flexible wire of the Lamp holder to the Ceiling rose to correspond to the L,N and E respectively.

Useful Links
W logo Electricity Wikipedia Show
W logo Electric Power Wikipedia Show
W logo Electricity Generation Wikipedia Show
W logo Electric Power Transmission Wikipedia Show
Electrical Components

Electrical Installation Work

Electrolesk
Generator Image
Installations
Standby Generator
RCD Tester
Digital Meters
RCD Testers
Socketoutlets and switches
Sockets and Switches
13A Switched Sockets