Electrolesk A Guide to Practical Electrical Installation Work.

Plier image

Wiring 5A Switched Socket Outlet

[5A Receptacle]

 

Background

Wiring of 5A Switched Socket outlet point is on the vane these days in Electrical Installation Work. Here we are considering wiring a 5A Socket Outlet [Receptacle] point for 50Hz, 230V AC Power Supply. Installation work described here is according to British Standards [ IEE Regulations and Practice ].

Material Requirement

For Industrial applications, 1.5 mm2 [called as 1.5 mm squared] Cross sectioned double insulated Cu [Copper] Cables [Cu/PVC/PVC] are used for the Phase [Live ] and the Neutral cables.

For Residential applications, 1.0 mm2 Cross sectioned double insulated Cu [Copper] Cables [Cu/PVC/PVC] are commonly used for the Phase and the Neutral cables.

Earth [Ground ]cable should be 2.5mm2 single insulated Cu[Copper] Cables [Cu/PVC] for both Industrial or Residential type of applications.

Cable lengths for the above circuits will be such that voltage drop along the cables will be with in the approved limits of 10% of Supply Voltage.

 

Accessory Requirement

PVC Box to install the 5A Socket outlet-01 nos

5A Switched Socket outlet-01 nos

MCB 6A -01 nos [ from a Distribution Board already installed]

 

 

Preparation

Install the socket outlet box at the required position. Lay 1/2" PVC conduit from the Distribution Board to the receptacle position. The conduits can be embedded into the wall structure and or lay outside, clipped to the wall or structure. Instead of PVC conduits and switch boxes, GI conduits and switch boxes are being used for Industrial type of installations where you need protection for cables from physical damage. In some wooden structured buildings, the cables are installed inside panels without conduits being used.The Cables should be colour coded correctly for Phase[Live],Neutral and Earth.

 

Method of Wiring -Residential

Make sure that the Power is isolated [ shut down] to the Distribution board or any circuit you will be working with.

Connect the Phase [L] wire to the outgoing side of a 6A or a 10A [Maximum] MCB from the Distribution Board [DB]. Draw the Phase wire to the socket outlet box and connect to terminal marked as L [Line] of the 5A receptacle.

Connect the Neutral [N] wire to the Neutral Link provided in the DB and draw the wire to the receptacle and connect to the terminal marked as N [Neutral].

Connect the Earth [E] wire to the Earth link provided in the Distribution Board. Draw Earth wire to the receptacle and connect to the terminal marked as E [Earth].

It is good practice to number the Phase and the Neutral wires at the DB for easy identification as one circuit.

 

PDF FilePDF

Schematic Diagram for 5A Switched Socket Outlet